﻿The behaviour of the dimming output at the end of the disabling function after successful confirmation can be configured.

*Switch off*: On acknowledgement, the dimming output is switched off and enabled again.

*Brightness value*: On acknowledgement, the dimming channel is set to the specified brightness value and enabled again.

*Memory value*: On acknowledgement, the active and internally stored brightness value prior to the last switch-off is set (via the "Switching" or "Central switching" object).

*Tracked brightness value*: On acknowledgement, the set state received during the disabling function or adjusted before the disabling function can be tracked at the end of the disabling with the appropriate brightness value. Any time functions still in progress will also be taken into account if necessary.

*No reaction*: On acknowledgement, the dimming channel shows no reaction and remains in the currently set state. Bus control of the dimming channel is enabled again.

*Flashing*: The dimming channel is released again for bus operation on acknowledgement and flashes on and off. The flashing time is configured generally for all channels on the parameter page "General". During the flashing, the logical switching state is "on 1" and the switch-on brightness is signaled back as brightness. A soft ON/OFF function is ignored during flashing. The flashing status remains active until another bus command is received and specifies another status.